Earth leakage unit and circuit breakers in a household distribution board

Why Does My Earth Leakage Keep Tripping? 8 Causes and Fixes

The earth leakage unit (ELU) in your DB board is the switch that saves lives. It trips when it senses current leaking to earth — through damp wiring, a faulty appliance, or a person. South African homes use 30 mA units for this reason. So a tripping ELU is doing its job. The question is what it's finding.

Safety first: resetting the switch and unplugging appliances is safe for anyone. Opening the DB board, testing circuits or replacing breakers is electrical installation work and must be done by a registered electrician.

Find the faulty circuit in 5 minutes

  1. Switch off every circuit breaker in the DB board.
  2. Reset the earth leakage.
  3. Switch the breakers on one at a time.
  4. When the ELU trips again, the last breaker you switched on is the faulty circuit.
  5. On that circuit, unplug everything, reset, and plug appliances back one by one.

The 8 most common causes

# Cause Clue Fix
1 Water in outdoor plugs or lights Trips after rain or irrigation Weatherproof IP-rated fittings and boxes
2 Faulty geyser element Trips when the geyser switches on Electrician replaces the element
3 Pool or borehole pump Trips when the pump starts Check the cable joints and motor insulation
4 Kettle, washing machine or heater Trips when one appliance is used Repair or replace the appliance
5 Damaged extension lead or multiplug Trips randomly Replace it
6 Too many appliances on one ELU Small leakages add up Electrician splits circuits across two ELUs
7 Lightning or a surge Trips during storms Fit surge protection
8 Worn-out earth leakage unit Trips with nothing on Replace the unit

Pumps are a common culprit

Borehole and pool pumps sit in wet places with long cable runs. A joint that wasn't sealed properly, a nicked submersible cable or a motor with failing insulation will leak current. If the ELU trips the moment the pump starts, switch the pump's isolator off and see if the problem stops. Then call your pump installer. Our borehole pump guide covers cable and control boxes.

Should I replace the earth leakage?

If the unit trips with every circuit off, or the test button doesn't trip it, it has failed and needs replacing. Your electrician can source a replacement 30 mA unit or a combined RCBO from our circuit protection range, alongside distribution boards.

Never bypass a tripping earth leakage, even for one night. It is the only device in your house that protects people, not wiring.

Press the test button monthly. If it doesn't trip, have it checked.

Related: Surge Protection for Your Home, Pumps and Solar · Top 5 Common Electrical Problems